All Services
Service

Fiber Optic Design, Splicing and Certification

Singlemode and multimode plant engineered against a real loss budget, fusion spliced, and certified to Tier 1 and Tier 2 so the margin is documented instead of assumed.

WHERE IT APPLIES
Campus NetworksData CentersIndustrialGovernmentHealthcare
Overview

Fiber either works or it does not, and when it does not, the cause is usually contamination or a splice that was never verified. Roughly the majority of field fiber faults trace back to a dirty or damaged endface — a defect invisible to the naked eye. We inspect every endface under a scope before mating, and we build to a calculated loss budget so there is measurable headroom for future splices and moves.

What the scope covers

Loss budget engineering

Link loss calculated from fiber attenuation, splice count, connector count and safety margin, then compared against the optics' power budget before the design is committed.

Fusion splicing

Core-aligned fusion with splice loss estimated at the machine and verified bidirectionally by OTDR. Mechanical splices only where a permanent repair is not possible.

Outside plant and inside plant

Direct-buried, duct, aerial and riser construction, with the transition to inside plant handled per code — including the unlisted-cable distance limit at the entrance.

Endface inspection

Every connector scoped to the IEC 61300-3-35 pass/fail criteria and cleaned until it passes. No exceptions, including factory-terminated assemblies.

Our Process

How the work actually runs

01

Route and media selection

OS2 singlemode for distance and future capacity, OM3/OM4/OM5 multimode where the optics and lengths justify it. Fiber count sized for growth, since the labor to place a cable dwarfs the cost of extra strands.

02

Design and budget

Route drawing, splice plan, strand assignment and the calculated loss budget the installation will be measured against.

03

Placement

Pulling tension and bend radius controlled, with the minimums respected — macrobend loss is a real and permanent penalty on singlemode.

04

Splicing and termination

Splicing in a controlled environment, trays organized and labeled, enclosures sealed and mapped.

05

Tier 1 and Tier 2 certification

Tier 1 insertion loss with an optical loss test set, bidirectional. Tier 2 OTDR traces to characterize every event along the span. Both delivered, with the loss budget shown alongside the measured result.

Standards & Compliance

  • ANSI/TIA-568.3-D — optical fiber cabling components
  • TIA-568 Tier 1 (OLTS) and Tier 2 (OTDR) certification methods
  • IEC 61300-3-35 — connector endface visual inspection criteria
  • NEC Article 770 — optical fiber cables and raceways
  • ANSI/TIA-758 — customer-owned outside plant

Code editions are revised periodically and local authorities amend them. The requirements that apply to your project are confirmed against your jurisdiction during design.

What You Receive

  • Bidirectional Tier 1 insertion loss results against the calculated budget
  • Tier 2 OTDR traces in native format with event tables
  • Splice matrix, strand assignment and enclosure maps
  • Endface inspection records
Common Questions

Is an OTDR trace enough on its own?

No. OTDR characterizes events along the span; it does not measure true end-to-end insertion loss. Tier 1 with a light source and power meter is the acceptance measurement. Tier 2 tells you where a problem is.

Why bidirectional testing?

A splice between fibers with different backscatter coefficients can read as a gain in one direction. Averaging both directions is the only way to get the real number.

Should we place more strands than we need?

Almost always. The cable is a fraction of the cost of the placement labor, and a dark strand is the cheapest capacity you will ever buy.

Talk to an engineer about fiber optic solutions.

Tell us the building, the constraints and the deadline. We will tell you what the work actually involves before anyone quotes a number.